LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 3
Control over the FLN Network
In the typical FLN network it is not necessary to modify any other parameters in the ACH580 Drive or E-Clipse to be able
to gather data from either the ACH580 drive or the E-Clipse bypass. If the drive was not available (failed), the points
listed in this document for the bypass would be available to the FLN network. The following parameters are only to be
modified if there is the need to start/stop the drive using the FLN network.
For run/stop over the FLN network for an ACH580 drive:
• E-Clipse bypass parameter 1601 must be set to 2: COMM
• To establish the frequency reference over the FLN network, the ACH580 drive parameter 28.11 must be set to
EFB 1.
For run/stop over the FLN network with E-Clipse to run the motor across the line:
• E-Clipse bypass parameter 1601 must be set to 2: COMM.
• E-Clipse bypass parameter 1625 must be set to 1: SYSTEM.
• E-Clipse bypass parameter 5003 must have a node ID assigned to it.
Topic 4 - Differences between FLN point support between ACH550 and ACH580 drive and E-Clipse bypass
Topic 5 & 6 includes a list of all points FLN points supported by the ACH580 drive as well as the E-Clipse bypass.
There are a few points that lack the functionality of the ACH550 and always report “0” in the ACH580 drive:
• Point 18 – Revolution counter (not supported in ACH580)
• Point 39 – Reference 2 source (only Reference 1 source bit is supported in ACH580)
• Point 48 – Maintenance trigger (not supported in ACH580)
• Point 88 – Alarm word 1 (not supported in ACH580)
• Point 89 – Alarm word 2 (not supported in ACH580)
There are a few points that lack the functionality of the 550 E-Clipse bypass and always report “0” in the ACH580 E-
Clipse bypass:
• Point 48 – Maintenance trigger (not supported in 580 E-Clipse)
• Point 88 – Alarm word 1 (not supported in 580 E-Clipse)
• Point 89 – Alarm word 2 (not supported in 580 E-Clipse)