LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 1
Technical Note 096
E-Clipse bypass configuration for GP1
Siemens FLN support
The purpose of Technical Note 096 is to provide guidance for the configuration of the ACH580-01 and ACH580-31 drive
with an E-Clipse (electronic bypass) package to utilize the GP1 fieldbus. The following topics will provide guidance on
how to implement the GP1 fieldbus in support of a Siemens FLN network. This document will refer to the drive as an
ACH580 drive and the electronic bypass (RBCU) unit as an E-Clipse.
Topics:
1. GP1 introduction & ACH580 E-Clipse support of FLN
2. EIA-485 network wiring configuration for ACH580 drive and E-Clipse
3. Programming of the E-Clipse to support FLN communication
4. Point support differences between ACH550 and ACH580 drive and E-Clipse
5. FLN point support for the ACH580 drive
6. FLN point support for the ACH580 E-Clipse
Topic 1 - GP1 introduction & ACH580 support of FLN
The ACH580-01 E-Clipse and ACH580-31 E-Clipse includes the GP1 fieldbus. This generic protocol will allow the ACH580
drive and E-Clipse to communicate on a Siemens FLN network.
Just a few points on why we need to do this:
1. Siemens is moving away from the FLN protocol and has stopped issuing new application numbers for new
products, such as the ACH580.
2. There is a significant installation base of older drives on existing FLN networks. GP1 allows the ACH580 to
replace those drives.
The GP1 embedded fieldbus connection to the ACH580 drive and E-Clipse bypass is based on an industry standard RS-485
physical interface. For ease of retrofit, the ACH580 uses the same interface (Siemens 2734 application number for the drive and
Siemens 2737 application number for the E-Clipse) as the ACH550. The ACH580 supports the majority of the FLN features that
were previously supported in the ACH550. The points list for both the ACH580 and its E-Clipse bypass are included in topics 5 &
6 of this document.
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 2
Topic 2 - EIA-485 network wiring configuration for the E-Clipse bypass
All communications wiring for GP1 support for the ACH580 drive and E-Clipse is done at the RBCU.
Figure 1 EIA-485 network wiring configuration for the E-Clipse bypass.
Topic 3 - Programming of E-Clipse bypass
All programming for GP1 for FLN support for an ACH580 drive with an E-Clipse bypass is programmed at the E-Clipse
bypass control panel.
Figure 2 Programming of the E-Clipse bypass to support FLN network communication using GP1
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 3
Control over the FLN Network
In the typical FLN network it is not necessary to modify any other parameters in the ACH580 Drive or E-Clipse to be able
to gather data from either the ACH580 drive or the E-Clipse bypass. If the drive was not available (failed), the points
listed in this document for the bypass would be available to the FLN network. The following parameters are only to be
modified if there is the need to start/stop the drive using the FLN network.
For run/stop over the FLN network for an ACH580 drive:
E-Clipse bypass parameter 1601 must be set to 2: COMM
To establish the frequency reference over the FLN network, the ACH580 drive parameter 28.11 must be set to
EFB 1.
For run/stop over the FLN network with E-Clipse to run the motor across the line:
E-Clipse bypass parameter 1601 must be set to 2: COMM.
E-Clipse bypass parameter 1625 must be set to 1: SYSTEM.
E-Clipse bypass parameter 5003 must have a node ID assigned to it.
Topic 4 - Differences between FLN point support between ACH550 and ACH580 drive and E-Clipse bypass
Topic 5 & 6 includes a list of all points FLN points supported by the ACH580 drive as well as the E-Clipse bypass.
There are a few points that lack the functionality of the ACH550 and always report 0 in the ACH580 drive:
Point 18 Revolution counter (not supported in ACH580)
Point 39 Reference 2 source (only Reference 1 source bit is supported in ACH580)
Point 48 Maintenance trigger (not supported in ACH580)
Point 88 Alarm word 1 (not supported in ACH580)
Point 89 Alarm word 2 (not supported in ACH580)
There are a few points that lack the functionality of the 550 E-Clipse bypass and always report 0 in the ACH580 E-
Clipse bypass:
Point 48 Maintenance trigger (not supported in 580 E-Clipse)
Point 88 Alarm word 1 (not supported in 580 E-Clipse)
Point 89 Alarm word 2 (not supported in 580 E-Clipse)
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 4
Topic 5 - FLN point support for the ACH580 drive
The following table lists the point database for ACH580 GP1 embedded field bus. (FLN: ACH550 application 2734)
ACH580 drive FLN points
Point
Subpoint Name
Factory
Engr.
Slope
Intercept
On
Off
Default
Units
Text
Text
#
Type
(SI Units)
01
LAO
CTLR ADDRESS
99
-
1
0
-
-
02
LAO
APPLICATION
2734
-
1
-
-
{03}
LAI
FREQ OUTPUT
0
Hz
0.1
0
-
-
{04}
LAI
PCT OUTPUT
0
PCT
0.1
0
-
-
{05}
LAI
SPEED
0
RPM
1
0
-
-
{06}
LAI
CURRENT
0
A
0.1
-
-
{07}
LAI
TORQUE
0
PCT
0.1
-200
-
-
{08} *
LAI
POWER
0 (0)
HP (KW)
0.134 (0.1)
0
-
-
{09} *
LAI
DRIVE TEMP
77 (25)
° F (° C)
0.18 (0.1)
32 (0)
-
-
{10}
LAI
DRIVE KWH
0
KWH
1
-
-
{11}
LAI
DRIVE MWH
0
MWH
1
-
-
{12}
LAI
RUN TIME
0
HRS
1
-
-
{13}
LAI
DC BUS VOLT
0
V
1
-
-
{14}
LAI
OUTPUT VOLT
0
V
1
-
-
{15}
LAI
PRC PID FBCK
0
PCT
0.1
-
-
{16}
LAI
PRC PID DEV
0
PCT
0.1
-
-
{17} *
LAI
MOTOR TEMP
77(25)
° F (° C)
1.8 (1)
32 0
-
-
{18}
LAI
MREV COUNTER
0
NOT SUPPORTED FOR ACH580
20
LAO
OVRD TIME
1
hrs
1
0
-
-
{21}
LDI
FWD.REV ACT
FWD
-
1
0
REV
FWD
{22}
LDO
FWD.REV CMD
FWD
-
1
0
REV
FWD
{23}
LDI
RUN.STOP ACT
STOP
-
1
0
RUN
STOP
{24}
LDO
RUN.STOP CMD
STOP
-
1
0
RUN
STOP
{25}
LDI
EXT1.2 ACT
EXT1
-
1
0
EXT2
EXT1
{26}
LDO
EXT1.2 CMD
EXT1
-
1
0
EXT2
EXT1
{27}
LDI
DRIVE READY
NOTRDY
-
1
0
READY
NOTRDY
{28}
LDI
AT SETPOINT
NO
-
1
0
YES
NO
30
LAO
CURRENT LIM
0
A
0.1
0
-
-
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 5
ACH580 drive FLN points
Point
Subpoint Name
Factory
Engr.
Slope
Intercept
On
Off
Default
Units
Text
Text
#
Type
(SI Units)
31
LAO
ACCEL TIME 1
300
sec
0.1
0
-
-
32
LAO
DECEL TIME 1
300
sec
0.1
0
-
-
{33}
LDI
HANDAUTO ACT
AUTO
-
1
0
HAND
AUTO
{34}
LDI
ENA.DIS ACT
DISABL
-
1
0
ENABLE
DISABL
{35}
LDO
ENA.DIS CMD
DISABL
-
1
0
ENABLE
DISABL
{36}
LDI
FLN LOC ACT
AUTO
-
1
0
FLN
AUTO
{37}
LDI
FLN CTL SRC
NO
-
1
0
YES
NO
{38}
LDI
FLN REF1 SRC
NO
-
1
0
YES
NO
{39}
LDI
FLN REF2 SRC
NO
NOT SUPPORTED FOR ACH580
{40}
LDO
RO 1 COMMAND
OFF
-
1
0
ON
OFF
{41}
LDO
RO 2 COMMAND
OFF
-
1
0
ON
OFF
{42}
LDO
RO 3 COMMAND
OFF
-
1
0
ON
OFF
{43}
LDO
RO 4 COMMAND
OFF
-
1
0
ON
OFF
{44}
LDO
RO 5 COMMAND
OFF
-
1
0
ON
OFF
{45}
LDO
RO 6 COMMAND
OFF
-
1
0
ON
OFF
{46}
LAO
AO 1 COMMAND
PCT
PCT
0.1
0
-
-
{47}
LAO
AO 2 COMMAND
PCT
PCT
0.1
0
-
-
48
LDO
RST RUN TIME
NO
NOT SUPPORTED FOR ACH580
49
LDO
RESET KWH
NO
-
1
0
RESET
NO
50
LAO
PRC PID GAIN
10
PCT
0.1
0
-
-
51
LAO
PRC PID ITIM
600
SEC
0.1
0
-
-
52
LAO
PRC PID DTIM
0
SEC
0.1
0
-
-
53
LAO
PRC PID DFIL
10
SEC
0.1
0
-
-
54
LDO
PRC PID SEL
SET1
-
1
0
SET2
SET1
55
LAO
EXT PID GAIN
10
PCT
0.1
0
-
-
56
LAO
EXT PID ITIM
600
SEC
0.1
0
-
-
57
LAO
EXT PID DTIM
0
SEC
0.1
0
-
-
58
LAO
EXT PID DFIL
10
SEC
0.1
0
-
-
59
LDO
LOCK PANEL
UNLOCK
-
1
0
LOCK
UNLOCK
{60}
LAO
INPUT REF 1
0
PCT
0.1
0
-
-
{61}
LAO
INPUT REF 2
0
PCT
0.1
0
-
-
{62}
LAO
EXT PID STPT
0
PCT
0.1
0
-
-
{63}
LAI
EXT PID FBCK
0
PCT
0.1
0
-
-
{64}
LAI
EXT PID DEV
0
PCT
0.1
0
-
-
66
LDO
SPD OUT MIN
0
PCT
0.1
0
-
-
67
LDO
SPD OUT MAX
1000
PCT
0.1
0
-
-
{68}
LDO
FLN LOC CTL
AUTO
-
1
0
FLN
AUTO
{69}
LDO
FLN LOC REF
AUTO
-
1
0
FLN
AUTO
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 6
ACH580 drive FLN points
Point
Factory
Engr.
Slope
Intercept
On
Off
Default
Units
Text
Text
#
(SI Units)
{70}
DI 1 ACTUAL
OFF
-
1
0
ON
OFF
{71}
DI 2 ACTUAL
OFF
-
1
0
ON
OFF
{72}
DI 3 ACTUAL
OFF
-
1
0
ON
OFF
{73}
DI 4 ACTUAL
OFF
-
1
0
ON
OFF
{74}
DI 5 ACTUAL
OFF
-
1
0
ON
OFF
{75}
DI 6 ACTUAL
OFF
-
1
0
ON
OFF
{76}
RO 1 ACTUAL
OFF
-
1
0
ON
OFF
{77}
RO 2 ACTUAL
OFF
-
1
0
ON
OFF
{78}
RO 3 ACTUAL
OFF
-
1
0
ON
OFF
{79}
RO 4 ACTUAL
OFF
-
1
0
ON
OFF
{80}
RO 5 ACTUAL
OFF
-
1
0
ON
OFF
{81}
RO 6 ACTUAL
OFF
-
1
0
ON
OFF
{82}
AI 1 ACTUAL
0
PCT
0.1
0
-
-
{83}
AI 2 ACTUAL
0
PCT
0.1
0
-
-
{84}
AO 1 ACTUAL
0
MA
0.1
0
-
-
{85}
AO 2 ACTUAL
0
MA
0.1
0
-
-
{86}
OK.ALARM
OK
-
1
0
ALARM
OK
{87}
OK.MAINT
OK
-
1
0
MAINT
OK
{88}
ALARM WORD 1
-
NOT SUPPORTED FOR ACH580
{89}
ALARM WORD 2
-
NOT SUPPORTED FOR ACH580
{90}
LAST FAULT
-
-
1
0
-
-
{91}
PREV FAULT 1
-
-
1
0
-
-
{92}
PREV FAULT 2
-
-
1
0
-
-
{93}
OK.FAULT
OK
-
1
0
FAULT
OK
{94}
RESET FAULT
NO
-
1
0
RESET
NO
{95}
MBOX PARAM
-
-
1
0
-
-
{96}
MBOX DATA
-
-
1
0
-
-
{98}
MBOX WRITE
DONE
-
1
0
WRITE
DONE
{99}
ERROR STATUS
-
-
1
0
-
-
a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
c. Point numbers that appear in brackets {} may be unbundled at the field panel.
d. Point numbers with *, ACH580 drive parameter 96.16 bit 0 determines if this value is metric or imperial.
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 7
Topic 6 - FLN point support for the ACH580 E-Clipse bypass
The following table lists the point database for E-Clipse GP1 embedded field bus. (FLN: ACH550 application 2734)
E-Clipse FLN points
Point
Subpoint
Name
Factory
Engr.
Slope
Intercept
On
Off
Default
Units
Text
Text
#
Type
(SI Units)
1
LAO
CTLR ADDRESS
2
-
1
0
-
-
2
LAO
APPLICATION 2737
2734
-
1
0
-
-
5
LAI
INPUT VOLT
0
V
1
0
-
-
{06}
LAI
CURRENT
0
A
0.1
0
-
-
{07}
LAI
SYSUNDRLOAD
NO
-
1
0
[YES]
[NO]
9*
LAI
PCB TEMP
77 (25)
° F (° C)
0.18 (0.1)
33 (0)
-
-
10
LAI
KW HOURS
0
KWH
1
0
12
LAI
RUN TIME
0
HRS
1
0
-
-
13
LAI
A.B. VOLT
0
V
1
0
14
LAI
B.C. VOLT
0
V
1
0
-
-
15
LAI
C.A. VOLT
0
V
1
0
-
-
20
LAO
OVRD TIME
1
HRS
1
0
-
-
{23}
LDI
MTR RUNNING
STOP
-
1
0
[RUN]
[STOP]
{24}
LDO
RUN.STOP CMD
STOP
-
1
0
[RUN]
[STOP]
{25}
LDI
OVERRIDE ACT
OFF
-
1
0
[ON]
[OFF]
{26}
LDO
OVERRIDE CMD
OFF
-
1
0
[ON]
[OFF]
{27}
LDI
SYSTEM READY
NOT READY
-
1
0
[READY]
[NOT READY]
{28}
LDI
SYS STARTED
NO
-
1
0
[YES]
[NO]
{29}
LDO
DAY.NIGHTDAY
DAY
-
1
0
[NIGHT]
[DAY]
30
LAO
BYP RUN DLY
0
SEC
1
0
-
-
{31}
LAI
BYPASSMODE
0
-
1
0
-
-
{32}
LDI
DRIVE.BYPASSDRIVE
DRIVE
-
1
0
[BYPASS]
[DRIVE]
{33}
LDI
BYP RUNNING
NO
-
1
0
[YES]
[NO]
{34}
LDI
RUN ENA ACT
DISABL
-
1
0
[ENABLE]
[DISABL]
{35}
LDO
RUN ENA CMD
DISABL
-
1
0
[ENABLE]
[DISABL]
{36}
LDI
FLN LOC ACT
AUTO
-
1
0
[FLN]
[AUTO]
{37}
LDI
FLN CTL SRC
NO
-
1
0
[YES]
[NO]
{40}
LDO
RO 1 COMMAND
OFF
-
1
0
[ON]
[OFF]
{41}
LDO
RO 2 COMMAND
OFF
-
1
0
[ON]
[OFF]
{42}
LDO
RO 3 COMMAND
OFF
-
1
0
[ON]
[OFF]
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 8
E-Clipse FLN points
Point
Subpoint
Name
Factory
Engr.
Slope
Intercept
On
Off
Default
Units
Text
Text
#
Type
(SI Units)
{43}
LDO
RO 4 COMMAND
OFF
-
1
0
ON
OFF
{44}
LDO
RO 5 COMMAND
OFF
-
1
0
ON
OFF
{48}
LDO
RST RUN TIME
NO
NOT SUPPORTED FOR E-CLIPSE
{49}
LDO
RESET KWH 0
0
-
1
0
-
-
{50}
LDO
START ENA 1
DISABL
-
1
0
[ENABLE]
[DISABL]
{51}
LDO
START ENA 2
DISABL
-
1
0
[ENABLE]
[DISABL]
{52}
LDO
START ENA 3
DISABL
-
1
0
[ENABLE]
[DISABL]
{53}
LDO
START ENA 4
DISABL
-
1
0
[ENABLE]
[DISABL]
{59}
LDO
LOCK PANEL O
0PEN
-
1
0
[LOCK]
[UNLOCK]
{68}
LDO
FLN LOC CTL
AUTO
-
1
0
[FLN]
[AUTO]
{70}
LDI
DI 1 ACTUAL
OFF
-
1
0
[ON]
[OFF]
{71]
LDI
DI 2 ACTUAL
OFF
-
1
0
[ON]
[OFF]
{72}
LDI
DI 3 ACTUAL
OFF
-
1
0
[ON]
[OFF]
{73}
LDI
DI 4 ACTUAL
OFF
PCT
0.1
0
[ON]
[OFF]
{74}
LDI
DI 5 ACTUAL
OFF
PCT
0.1
0
[ON]
[OFF]
{75}
LDI
DI 6 ACTUAL
OFF
MA
0.1
0
[ON]
[OFF]
{76}
LDI
RO 1 ACTUAL
OFF
MA
0.1
0
[ON]
[OFF]
{77}
LDI
RO 2 ACTUAL
OFF
-
1
0
[ON]
[OFF]
{78}
LDI
RO 3 ACTUAL
OFF
-
1
0
[ON]
[OFF]
{79}
LDI
RO 4 ACTUAL
OFF
-
1
0
[ON]
[OFF]
{80}
LDI
RO 5 ACTUAL
OFF
[ON]
[OFF]
{86}
LDI
BYPASS ALARM
OK
[ALARM]
[OK]
{88}
LAI
ALARM WORD 1
NO
NOT SUPPORTED FOR E-CLIPSE
{89}
LAI
ALARM WORD 2
NO
NOT SUPPORTED FOR E-CLIPSE
{90}
LAI
LAST FAULT
-
-
1
0
-
-
{93}
LDI
OK.FAULT BYP
OK
-
1
0
FAULT
OK
{94}
LDO
RESET FAULT
NO
-
1
0
RESET
NO
{99}
LAO
ERROR STATUS
-
-
1
0
-
-
a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
c. Point numbers that appear in brackets {} may be unbundled at the field panel.
d. Point numbers with *, ACH580 drive parameter 96.16 bit 0 determines if this value is metric or imperial.
LVD-EOTKN096U-EN REV A
Effective: 2022-09-30 9
Conclusion
This document provides the information needed to support the wiring and programming of the ACH580 E-Clipse bypass
package using native fieldbus GP1 for the support of an existing Siemens FLN network. The ACH580 drive and E-Clipse
bypass support this through the same interface (Siemens 2734 application number for the drive and Siemens 2737
application number for the E-Clipse) as the ACH550.