SYSTEM 238 Installation Manual
BLK
RED
BATTERY
DIRECT
CONNECT
DEVICES
UNSWITCHED
AUX
POWER
- Protected by Fuse F2:
3 AG, 0.75 A
- Shared with keypads
and AUX POWER
KEYPAD
INFORMATION
- Do not exceed 4
keypads
or max AUX POWER
- Protected by Fuse
F3: 3 AG, 0.75 A
WARNINGS:
- For continued protection
against risk of fire, replaces
fuses only with fuses of same
type and rating
- Disconnect AC, battery, and
phone cord BEFORE servicing
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
Capacity for
emergency standby
at least 4 hours
- Connect ground wire from door hinge to earth ground using
16 AWG, green jacketed, solid-conductor wire
GENERAL INFORMATION
- All outputs are power limited
- If programmed for EOL or Supervised loop, the 2.2K ohm EOL
resistor (Model 9.X, 2.2K) must be at end of circuit
- Loop 8 can be used as standard loop or used for switched 10-
12.5 VDC at 50 mA for 2-wire powered devices. Loop 8 can
support up to 10 BRK Model 2400 2-wire smoke detectors.
- Loop voltages:
Loops 1 - 8
0 - 2.5 VDC = short
2.5 - 8.5 VDC = normal
8.6 - 15 VDC = open
- Install transformer on unswitched power receptacle
- Only use 12 VDC, 6.5 AH sealed lead-acid battery
POWER SUPPLY INFORMATION
- Replace battery every 3 - 5 years with C&K Model 1265
- Standby time with 1 keypad is 16 hours at 250 mA
- Power demand for AUX POWER, keypads, and sounders
not to exceed maximum ratings
Fuse F4
3 AG, 3 A
battery protection
- are electrically common
AUDIBLE
10.5-13.5 VDC
Protected by Fuse
F1: 3AG, 2.5 A
16.5 VAC
25 - 40 VA
50 / 60 Hz
SWITCHED
AUX
POWER
P/N 5-051-162-00 Rev K
PHONE
CORD
- 9.X PCF
Red = incoming ring
Green = incoming tip
Gray = seized ring
Brown = seized tip
Blue = tamper
Orange = tamper
WARNING: Circuit Damage May Result
From Incorrect Wiring Connections.
- Remove AC and battery power before replacing fuses
- Maximum battery charge current = 350 mA
CAUTION:
Total power from Bell, Sw/Aux, Aux
and Key+ Terminals NOT to exceed
800 mA, combined
12 VDC
6.5 AH
sealed lead-acid
F2 0.75 A
KEYPAD
F1 2.5 A
BELL FUSE
F2 0.75 A
AUX DEVICES
SYSTEM 238 Installation Manual
2
Subject Page No.
System 238 Terminal Label Front Cover
Residential and Commercial Installation Guidelines 2
Installation 2 - 3
Wiring the Panel 3 - 4
System Start-Up 4
Keypad Setup 4 - 5
Addressing Keypads 5
Factory Default Settings 5
Programming Options (Alphabetical List) 5 - 6
Programming the Panel 6
Programming with the LED Keypad 6
Programming with the Alpha Keypad 6
Entering Hexadecimal Numbers 6
Programming the Alpha Keypad 6 - 7
Programming Letters & Numbers 7
Special Function Keys 7
Programming Options (Numerical Order) 8 - 18
Keypad Label Drawer 19
Telephone Line Problems 19
Watchdog Indicator 19
Keypad Operation Command Summary 20
Help with Common Problems (Troubleshooting) 21 - 22
Reducing False Alarms 23 - 24
Programming Worksheets 26 - 27
Table of Contents
Scope of This Manual
This manual contains basic installation and programming information
for the SYSTEM 238. For additional information about using or
programming the system, please refer to the SYSTEM 238 Keypad
Manual, Alpha Keypad Manual, or Commander II/Monitor II Operating
Manual.
BEFORE YOU START
12. The system must not be programmed to dial a police
station.
13. Use screws (supplied) to secure cover or install a lock on
the cabinet.
14. Loop Response Time should be set to 500mS.
Accuracy
This manual has been carefully checked for accuracy. However, C&K
SYSTEMS assumes no liability for inaccuracies or actions resulting
from the use of this manual. In addition, C&K reserves the right to modify
the SYSTEM 238 hardware, software, and manuals without prior
notice.
The following list of options are recommended for a standard SYSTEM
238 installation in a residential environment:
Residential Configuration
1. Program the audible to sound for at least four minutes
before silencing.
2. No zones should be programmed for silent alarm.
3. Fire zones should be programmed for Temporal Code 3
audible alarm.
4. Burglar zones should be programmed for a steady
audible.
5. Burglar loops should be programmed for EOL.
6. Entry Delay should not be greater than 45 seconds.
7. Exit Delay should not be greater than 60 seconds.
8. The Dynamic Battery Test should be enabled.
9. The Unit Status Report should be enabled.
10. The 24-hour Check-in (Test Report) should be enabled.
11. The communicator should not be programmed for Delay
Before Dial.
The following additional options are recommended for commercial
installations.
Mounting
The SYSTEM 238 should be mounted in a location which allows
convenient access to AC power, telephone connections, and earth
ground.
Remove the circuit board from the cabinet. This will prevent
possible damage to the PCB when removing the knock-outs.
Remove the knock-outs, as required.
Mark the screw mounting holes on the wall.
Mount the cabinet at the desired height and pass the cables
through the knock-outs.
Replace the circuit board, remembering to connect the ground
lug to the lower left corner of the circuit board.
Reconnect the spade lug to the lower door hinge. This provides
the earth ground connection for the door.
INSTALLATION
Zone Programming
1. The audible should be programmed to sound at least 15
minutes before silencing.
2. The ring-back function should be activated.
3. The control panel should be mounted in an enclosure that is:
(a) Attack-resistant (C&K Model # 2330-UAC)
(b) Secured with a key-lock and six (6) #6 X 1¼" sheet
metal screws.
(c) Tamper protected against cabinet door opening and
removal from mounting surface.
(d) For safe and vault applications the control panel must be
monitored by a UL Listed shock sensor suitable for the
protection of sheet metal enclosures.
4. The Ademco Model AD10-12 bell with Model AB bell housing
should be used.
5. The power and tamper wiring between the bell and the
control panel should be completely enclosed in rigid conduit
or electric metallic tubing for a Grade A system or flexible
conduit for a Grade B system.
6. Zone(s) monitoring tamper circuitry should be 24 hour and
non-shuntable.
FIRE LOOP BURGLAR LOOP
No Delay Before Dial
24-hour arming
Pulsing audible
Supervised
- latching for heat
- resetting for smoke
Not shuntable
500mS Loop Response Time
No Delay Before Dial
NO/NC with EOL
Steady audible
500mS Loop Response Time
SYSTEM 238 Installation Manual
3
Earth Ground
To ensure the effectiveness of the lightning and transient protection
circuits, the control panel must be connected to "Earth Ground".
Ideally, this should be a common ground to the power lines, telephone
system, and security system. This type of ground, called a "Unified
Earth Ground", provides the best protection. The ground connection,
from a grounding rod, cold water pipe or other established ground
point, is made to the green jacketed wire providing a ground to the
panel housing.
WIRING THE PANEL
Standby Battery
The SYSTEM 238 is designed to operate with a 12 volt, 6.5 Ah, sealed
lead-acid battery (C&K Model 1265). Do not use non-rechargeable
batteries or batteries other than sealed lead-acid. It is recommended
that you replace the standby battery every three to five years.
Connect the red lead to the battery positive terminal and the black lead
to the battery negative. The battery is reverse-polarity protected by
a 3 AG, 3 amp, fast-blow fuse (F4).
Connecting to
Earth Ground
Power
Lines
Control
Panel
Unified Earth Ground
with Bonded Ground Roots
Telephone
Earth Ground
Power Line
Earth Ground
Telephone
Lines
Terminal Label:
AC
AC power is supplied by a 16.5 VAC, 25 - 40
VA transformer at 50 or 60 Hz. The transformer
must be a UL listed Class 2 transformer. Connect
the secondary of the transformer to the terminals
labelled AC. Use at least 18 AWG (1.02 mm) wire to reduce voltage
drops. The primary side of the transformer must be connected
to an unswitched receptacle. Do not connect primary to
Ground-Fault-Interrupt (GFI) circuits. Secure the transformer
to the wall.
AC POWER
AC Power Failure
If an AC power failure lasts more than 15 minutes, the keypads will
display a system trouble. An AC failure report will be sent, if pro-
grammed. When AC is restored for five minutes, a restoral report will
be sent.
Precautions
Do not share the secondary of the transformer with other
devices. A foreign ground can damage the power
supply, voiding the warranty.
Do not use any transformer other than that specified in
the AC POWER section above.
Available Power
The maximum total power available from the Audible, AUX (Switched
and Unswitched), and Keypad is 800 mA. The switched auxiliary,
unswitched auxiliary, and keypads share the same power bus.
Combined power for these outputs should not exceed 500 mA.
NOTE: The 50 mA switched power available on Loop 8 is
part of the total 500 mA AUX power.
Terminal Label:
BELL & C
AUDIBLE OUTPUT
The BELL terminal provides up to 1.3 amps at
10.5 - 13.5 VDC . The type of voltage (steady,
pulsed, chirp) and the time is programmable.
Fuse F1
The BELL terminal is protected by a 2.5 amps, 3 AG fast-blow fuse
(F1).
NOTE: If any fuse opens, remove AC and DC power, remove
the short or overload condition, then replace the fuse
before restoring power. Do not substitute a higher
rated fuse.
Electromagnetic Interference
Vibrating horns can produce electromagnetic interference (EMI).
While EMI will not damage the SYSTEM 238, it can cause transmission
errors and mis-dialing. To minimize EMI, install a 0.01 mfd, 100 volt
capacitor across the terminals of the horn. The capacitor must be
located in the horn.
AUXILIARY POWER
The SW/AUX terminal provides positive 10 - 12.5
VDC power for devices that require switched power
for resetting. Typical devices are glass-break and
smoke detectors.
The C terminal provides power common.
The AUX terminal supplies uninterrupted positive power.
Fuse F2
The SW/AUX and AUX terminals are protected by a 0.75 amp, 3 AG,
fast-blow fuse (F2).
ARMING STATIONS
Connect the keypad to the System 238 control panel as shown in the
diagram at the top of the next page.
Maximum wire length for connecting any keypad is 500' (152 m) of 22
AWG (0.643 mm) copper wire.
Terminal Labels:
SW/AUX, C & AUX
Terminal Labels:
C, KEY+, DATA, & CLK
The KEY+ terminal (red) provides 11 - 14 VDC
keypad power.
The DATA terminal (green) is data from the
keypad to the panel.
The C terminal (black) is common.
The CLK terminal (white) is the clock line.
SYSTEM 238 Installation Manual
4
Keypad Wiring
+
When operated as a Super-
vised Loop, an open will be
reported as a Trouble.
Whether the system is armed
or disarmed. A short on a
Supervised Loop will be re-
ported as an alarm if the
system is armed, but will have
no effect if the system is dis-
armed.
-
Supervised Loop
N.C.
Trouble
N.O.
Alarm
Loop 8
Terminals C and Z8 are a standard loop that can also power 2-wire
devices. It supplies 10 - 12.5 VDC at 50 mA. Use Loop 8 to power
2-wire glass-breaks and smoke detectors.
The SYSTEM 238 is capable of addressing up to 8 Alpha keypads.
LED keypads do not require addressing. Each LED keypad uses 35
mA of current. Each LCD keypad uses 64 mA of current. See
Available Power for current limitations. See page 5 for additional
information on keypad setup.
LOOP INPUTS
Each loop is independently
configured through pro-
gramming. Loops can be
wired with an open circuit
switch, or closed circuit
switch, or with a 2.2K ohm
end-of-line (EOL) resistor.
When programmed as EOL,
either an open or a short will
be reported as an alarm if
the system is in an armed
state.
-
+
N.O.
Alarm
N.C.
Alarm
EOL Loop
Terminal Labels:
Z 1 - Z 8 & C
Fuse F3
The KEY+ terminal is protected by a 0.75 amp, 3 AG, fast-blow fuse
(F3).
Connect the keypad to the control panel as shown in the diagram
above. The Alpha Plus keypad also has a jumper, located near the
piezo, that must be removed when used with the System 238 control
panel.
1. Position the tamper switch inside the cabinet at the lower right
corner of the cabinet. For the wall tamper, the plunger should go
through the small hole in the back of the cabinet. For the door
tamper, the plunger should face out from the cabinet. Refer to
the drawing below.
2. Connect the tamper switches in series and wire the tamper
terminals to a dedicated zone of the control panel.
3. Program the dedicated zone as desired: NC, EOL, 24-hour, etc.
Once the tamper switches are installed, opening the cabinet door or
removing the cabinet from the wall will result in a tamper signal at the
panel.
TAMPER SWITCH INSTALLATION
C&K has designed the SYSTEM 238 cabinet to use the Ademco
Model 19 tamper switch. The cabinet is constructed in order to
accommodate two switches. One tamper for the cover and a second
switch for a wall tamper. To install the tamper switches:
Tamper Switches installed in the SYSTEM 238 cabinet
LEAD-ACID
BATTERY
PRINTED CIRCUIT
BOARD
WALL
TAMPER SWITCH
DOOR
TAMPER SWITCH
TELEPHONE INTERFACE
Connect the SYSTEM 238 to the phone line using the
9.X PCF cord (not included). The cord has an 8-pin
telco plug on one end. Plug the telco end directly into
the phone companies RJ31 or RJ38X jack. Connect
the flying leads to the SYSTEM 238 PCB as shown
below and listed on the next page.
TB1
RJ-38X Wiring
Diagram
T
R
T1
R1
Incoming
Telco Line
1
23
4
8
7
6
5
T1
R1
T1 = Seized Tip
R1 = Seized
Ring
Red
Green
Protector
Ring
Tip
Tamper Jumper
House
Phones
SYSTEM 238 Installation Manual
5
Adjusting the LCD Display
To adjust the viewing angle, remove the keypad from the back
mounting plate. Towards the bottom center of the circuit board is
a small hole. Insert a small screwdriver into the hole and adjust
R23, while holding the keypad at its mounting height. Adjust the
potentiometer as necessary for optimum viewing.
Addressing Keypads
Each Alpha keypad installed in the system must have an address.
Addresses must not be repeated. When replacing a keypad,
make sure the replacement keypad has the same address as the
previous keypad.
The first time you power up the system, unaddressed Alpha
keypads will display KEYPAD ADDRESS?. Press any number
from 0 through 7 at each keypad. The exact number you press
is not important as long as each keypad has a different address
number. The keypad will not accept values outside of the specified
range. Should you accidently use the same address for more than
one keypad, the system will fail to properly respond to the keypad
input. Refer to page 23 for assistance in correcting this problem.
Once all keypads have been addressed, reset the panel by
pressing [Master Combination] [*] [6] [8] [#] or by tempo-
rarily removing both AC and DC power.
FACTORY SETTINGS
DEFAULT PROGRAM SETUP
The default programming of the SYSTEM 238 will allow you to
operate it as a local panel without any additional programming.
The actual default programming values are shown on the Pro-
gramming Worksheet (last 2 pages of this manual).
Note: If you connect power before wiring the loops, install
a 2.2K EOL resistor across each loops.
Combinations
Installer combination: 0 1 2 3 4 5
User #1 (Master) combination: 1 2 3 4
Users #2 - 8: disabled
Default installer combination: yes
Guest combination: no
Combination required: no
Arming type: goof-proof
Opening/Closing: disabled
Duress: disabled
Reporting
Account #1 and #2: disabled
Dialing type: pulse
RPS allowed: yes
Zones
Zone 1 = Entry/Exit delay - EOL circuit
Zone 2 = doors or windows - EOL circuit
Zone 3 = doors or windows - EOL circuit
Zone 4 = doors or windows - EOL circuit
Zone 5 = interior - EOL circuit
Zone 6 = interior - EOL circuit
Zone 7 = 24-hour panic or tamper - EOL circuit
Zone 8 = fire or smoke - supervised EOL circuit
Emergency soft zone: chirp audible
Fire soft zone: pulsed audible
Police soft zone: steady audible
Testing
Test report interval: 7 days and disabled
Timing
Entry time: 60 seconds and prewarn
Exit time: 30 seconds and prewarn
Bell time: 5 minutes
Unit Control
Local system: yes
Dynamic battery test: off
PROGRAMMING OPTIONS
The following is an alphabetical listing of all SYSTEM 238 program-
ming options, including Command Locations and Digit Positions.
Digit Positions are inside parentheses ( ).
Option Location
Account #1 0C (1-6)
Account #2 10 (1-6)
Alarm Code by Loop 17 - 1E (1-2)
Alarm Loop Shunting by Loop 30 - 37 (2)
Alarm Receiver Select by Loop 1F - 26 (1)
Audible Time 2D (5)
Audible Type by Loop 1F - 26(5)
Bell Reverse Operation 2E (3)
Cancel Receiver Select 2A (6)
Cancel Report Code 2A (5)
Closing Report Code 2C (3)
Closing Report Receiver 2C (4)
ALPHA KEYPAD INFORMATION
The Alpha keypad uses a top viewing display. This means the display
reads most clearly when viewed from a top angle rather than straight
on or from below. Mounting the keypad at the light switch level and
adjusting the viewing angle gives the best viewing results.
KEYPAD SETUP
Voltage Variations
Output voltages at the Sw/AUX, AUX, and KEY+ terminals may vary
between 9.0 and14.4 VDC (worst case), depending on the load,
battery condition, and AC line voltage.
SYSTEM START-UP
Five minutes after the panel is powered up, it will dynamically test the
standby battery by interrupting AC power for two minutes and
monitoring the battery under load.
Standby Battery Time with One LED Keypad
AUX POWER DRAIN*
50 mA 32 hours
STANDBY TIME
* Total power for all keypads, auxiliary, and Loop 8
150 mA
250 mA
500 mA
24 hours
16 hours
10 hours
If you replace the battery after a SYSTEM TROUBLE - LOW BATTERY
message, you must test the battery under load conditions. Press [*]
[6] [4] [#] to start the Dynamic Battery Test.
9.X PCF
The 9.X PCF has eight flying leads. Wire them to the PCB terminals
as follows:
GRAY = ring seized
GREEN = tip
RED = ring BROWN = tip seized
BLUE and ORANGE = tamper
YELLOW and BLACK = not used
SYSTEM 238 Installation Manual
6
Option Location
Combination Command 09 (2)
Daily Battery Test Enable 2F (2)
Delay Before Dial by Loop 30 - 37 (4)
Delay Before Dial Time 0B (1)
Dial Attempts 0B (6)
Dial Type 0B (2)
Disable Loop LEDs 2E (5)
Door Chime Enable by Loop 30 - 37 (1)
Duress Report Code 2D (1)
Duress Report Receiver 2D (2)
Emergency Bell Type 27 (4)
Emergency Report Code 27 (1 - 2)
Emergency Receiver Select 27 (3)
Entry Delay Time 2D (3)
Entry Pre-alarm Enable 2E (1)
Exit Delay Time 2D (4)
Exit Pre-alarm Enable 2E (2)
Faulted Arming Type 09 (4)
Fire Bell Type 28 (4)
Fire Report Code 28 (1 - 2)
Fire Receiver Select 28 (3)
Four Minute Power Up Delay Enable 2F (3)
Group Shunt Enable 30 - 37 (3)
Guest Combination 08 (2 - 6)
Guest Combination Time 09 (1)
Installer Combination 00 (1 - 6)
Keypad RPS Enable 0B (3)
Local System Only 2F (1)
Loop Arming Type 1F - 26 (4)
Loop Audible Type 1F - 26 (5)
Loop Circuit Type 1F - 26 (6)
Loop Receiver Select 1F - 26 (1)
Loop Response Time 1F - 26 (2)
Loop Restore Type 1F - 26 (3)
Master Code (User #1) 01 (2 - 6)
Opening Report Code 2C (1)
Opening Report Receiver 2C (2)
Police Bell Type 29 (4)
Police Report Code 29 (1 - 2)
Police Receiver Select 29 (3)
Phone Ring Type 0B (5)
Receiver #1 Message Format 0A (2)
Receiver #1 Phone Number 0D - 0F (1 - 6)
Receiver #1 Receive Format 0A (1)
Receiver #2 Message Format 0A (4)
Receiver #2 Phone Number 11 - 13 (1 - 6)
Receiver #2 Receive Format 0A (2)
Restoral Reporting Code by Loop 17 - 1E (3 - 4)
Restore Receiver Select 2A (2)
Ring Back Enable 2E (4)
RPS Enable 0B (4)
RPS Phone Number 14 - 16 (1 - 6)
Set Test Report Countdown Timer A0 (1)
Shunt Enable 30 - 37 (2)
Shunt Receiver Select 2A (1)
Shunt Reporting Code 17 - 1E (5 - 6)
Soft Zone Operation Enable 2F (4)
Test Report Code 2B (1 - 2)
Test Report Interval 2B (4)
Test Report Receiver Select 2B (3)
Unit Status Code 2A (3)
Unit Status Receiver 2A (4)
User Arming Type 01 - 08 (1)
User Combinations 01 - 08 (2 - 6)
You can program the SYSTEM 238 from the LED or Alpha keypad,
or remotely using the COMMANDER II software. Remote program-
ming information can be found in the COMMANDER II/MONITOR II
Operating Manual. This manual contains a brief description of each
programming option beginning on page 8.
PROGRAMMING THE PANEL
All panel wiring for the SYSTEM 238 should be completed prior to
applying power. You can only access the programming mode
when the control panel is disarmed.
NOTE: Command Location A0 must be addressed directly. When
programming this Command Location with an Alpha keypad, the
previously stored data is not displayed. To program this location,
enter the Command Location followed by the [#] key. Then enter the
data to be stored and again press the [#] key.
Warning: If you enter a Command Location and then press the [#]
key without entering any program data, the keypad will beep 5 times,
indicating an error. To correct this problem, simply re-enter the
Command Location and Data, then press the [#] key.
Programming with the LED Keypad
Programming with an LED keypad is a one-step process. Key in the
two-digit address (Command Location), followed immediately by the
desired programming values (program data), then press the [#] key
to store the data. The LED keypad does not display any pro-
grammed values. If you are not sure that the correct programming
values have been entered, program the Command Location again.
To Start Keypad Programming
Key in the [Installer Combination] [*] [0] [#]. The default Installer
Combination is 0 1 2 3 4 5. The programming mode is indicated
by the Program LED being lit on the LED keypad or CMD DATA
being displayed across the top row of the LCD display for the
Alpha keypad.
Programming with the Alpha Keypad
Entering program data with an Alpha keypad is a two-step process.
First, key in the two-digit address (Command Location) to be
programmed and press the [#] key. The Alpha keypad displays the
Command Location and the data previously stored. Enter the new
data you wish to store and press the [#] key to write the data. You
can also scroll through the Command Locations in numerical order
by alternately pressing and releasing the [#] key.
NOTE: To program Command Location A0 with an LED keypad,
remember to enter the Command Location, followed by the program
data, then press the [#] key.
Data is programmed into the panel using the hexadecimal number
system, which consists of the digits 0 - 9 and the letters A - F. The
digits 0 - 9 are entered directly from the keypad. The chart below
shows how to enter the hexadecimal digits A through F.
Programming Hexadecimal Numbers
The Alpha keypad may be used to program the control panel. The
cursor is moved using the "E" and "P" keys, as indicated in the
figure below. The "F" key enters a blank space and moves the
cursor one position to the right.
SYSTEM 238 Installation Manual
7
PROGRAMMING the ALPHA KEYPAD
Keypad Message Programming
The Alpha keypad programming template is used to allow the in-
staller to program messages and zone descriptions into the Alpha
keypads. The template shown below should be used when pro-
gramming the keypad.
To activate the keypad programming mode, enter the [Installer's
Code] [*] [0] [1] [#]. Information may be entered into the key-
pad in the form of letters (upper and lower case), numbers (0 -
9), and 22 special symbols. All characters are displayed in the
order listed above, i.e. upper and lower case letters, numbers,
and special symbols. The [Space] character precedes the letter
A.
To enter a Message or Label, use the [2] key to scroll through the
characters until you reach the desired character. If you scroll past
the desired character, the [8] key may be used to scroll back-
wards.
When the desired character is displayed, press the [6] key to move
the cursor to the next character position. The [4] key moves the
cursor to the left. When all characters have been entered, press
the [#] key to write the message and move to the next message
position. Use the [0] key to move backward through the messages.
Ensure the Alpha keypad is wired to the SYSTEM 238 and power is
applied to the control panel. You can only access the programming
mode when the control panel is disarmed.
NOTE: Programming the Keypad is not the same as Keypad
Programming.
123
4
56
789
0
ALPHAII Programming Template
ALPHAPLUS Programming Template
12 3
65
4
78 9
0
NOTE: If you do not press any key for 5 minutes, the
keypad will automatically exit the programming
mode.
To Exit Keypad Programming
When you have finished programming, press [*] [#]. The keypad
will also exit the programming mode if you do not press any
key within a five minute period.
The Alpha Keypad
You can program the Alpha keypads for special messages, each
of the 8 zone labels, and the keypad address. Zone Labels
display during the walk-test and when the [#] key is pressed
during alarm memory or faults. The programmable Service
Message is displayed during AC failure, fuse failure, communica-
tion failure, or low battery. The Dealer Message displays when the
system is disarmed. The keypad address is initially displayed only
during system start up (see page 5, Keypad Addressing).
These messages can be programmed directly from the Alpha
keypad or remotely using the Commander II/Monitor II software
package. For more detailed information about remote program-
ming, refer to the Commander II/Monitor II Operating Manual.
The Scrolling order of the Alpha Plus messages is:
SERVICE MESSAGE
DEALER MESSAGE
SOFT ZONE IDENTIFIER (C)
HARDWIRED LOOP IDENTIFIERS
KEYPAD ADDRESS
Both the Alpha and the Alpha Plus use the same procedure to
program messages.
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
The last two Command Locations are CL 37 and CL A0. Pressing
the [#] key at these locations will advance you to CL 38 or CL A1,
respectively. Locations CL 38 and CL A1 are not used in the
SYSTEM 238. If you accidentally enter either of these locations,
press [*] [#] to exit programming, or enter the Command
Location number, followed by the [#] key, for the location you wish
to program.
SYSTEM 238 Installation Manual
8
Command Locations 00 - 08
Command Location 00: Installer Combination
(1) (2) (3) (4) (5) (6)
012345
00
Default Values
Digit Position (1): First Digit of Installer Combination
0
Hard-coded to "0". Installer's combination will always start with 0.
Combination must have 5 digits in addition to Position (1).
Valid entries are 0 - 9.
Digit Positions (2) - (6): Remaining Digits in Combination
Command Location 01 - 08: User Arming Type and Combination
Digit Position (1): Arming Type
(1) (2) (3) (4) (5) (6)
91234E
10
1
**Default Values
01 = User #1 (Master)
02 = User #2
03 = User #3
04 = User #4
1 = Arm Only, No Closing (C) Report, No Shunting
2 = Disarm Only, No Opening (O) Report, No Shunting
3 = Arm and Disarm, No O/C Reports, No Shunting
05 = Us er # 5
0 6 = U s e r # 6
0 7 = U s e r # 7
08 = User #8 (Guest)
4 = Arm Only, with Closing Report, No Shunting
5 = Disarm Only, with Opening Report, No Shunting
6 = Arm and Disarm, with O/C Reports, No Shunting
7 = Arm Only, No Closing Report, Shunting Allowed
8 = Disarm Only, No Opening Report, Shunting Allowed
9 = Arm and Disarm, No O/C Reports, Shunting Allowed
0 = Arm Only, with Closing Report, Shunting Allowed
1 = Disarm Only, with Opening Report, Shunting Allowed
2 = Arm and Disarm, with O/C Reports, Shunting Allowed
Digit Position (2): First Digit of Arming Code
Hard-coded to User's PIN. You cannot change this number.
Digit Positions (3) - (6): Remaining Digits in Combination
Comination may have from 1 - 4 digits in addition to Position (2).
Valid entries are 0 - 9.
**Default Values are different for
each user. Refer to the SYSTEM
238 Programming Worksheet at the
end of this manual for other user
default values.
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
NOTE: Some programming locations allow variable-length data and require an
End-of-Number (EON) character. Program 4 ("E") after the last digit.
Fill remaining unused Positions with "0". The EON character is not required
if the last digit is in Position (6).
SYSTEM 238 Installation Manual
9
Command Locations 09 and 0A
Command Location 09: Arming/Combination Options
(1) (2) (3) (4)
00 11
Default Values
09
Digit Position (2): Combination Command
0 = No
1 = Yes; requires combination for Bypass, Group Bypass, Instant Arm, keypad
activated RPS, and Test (central station and bell)
Digit Position (3): Default Installer Combination
0 = No; this enables the Pirate-Guard
TM
feature for added security
1 = Yes; combination changes back to factory value on power loss
Digit Position (4): Faulted Arming Type
1 = Goof-Proof: zones must be normal or shunted to arm
2 = Force Arm: faulted zones will be shunted at end of Exit Delay
3 = Chirp Alert: faulted delay zones will chirp bell during Exit Delay
Command Location 0A: Communications Formats
(1) (2) (3) (4)
12 12
Default Values
0A
Digit Position (1): Receiver #1 Receiver Format
Digit Position (2): Receiver #1 Message Format
1 = 3/1 single
2 = 3/1 extended
3 = 4/2 (2-digit reporting code)
4 = 4/1
5 = CFSK III
6 = 4/9 Ademco DTMF
7 = 4+2 SumCheck
5 = CFSK III
6 = DTMF, 1400 Hz
3 = SumCheck, 1400 Hz
4 = SumCheck, 2300 Hz
1 = Fast "A", 2300 Hz
2 = Slow "B", 1400 Hz
Digit Position (3): Receiver #2 Receiver Format
1 = Fast "A", 2300 Hz
2 = Slow "B", 1400 Hz
3 = SumCheck, 1400 Hz
4 = SumCheck, 2300 Hz
5 = CFSK III
6 = DTMF, 1400 Hz
Digit Position (4): Receiver #2 Message Format
3 = 4/2 (2-digit reporting code)
4 = 4/1
1 = 3/1 single
2 = 3/1 extended
5 = CFSK III
6 = 4/9 Ademco DTMF
7 = 4+2 SumCheck
(DTMF)
(DTMF)
0 = Guest Time Disabled
1 = 1 day
2 = 2 days
3 = 3 days
4 = 4 days
5 = 5 days
6 = 6 days
7 = 7 days
8 = 8 days
9 = 9 days
Digit Position (1): Guest Combination Time
0 = 10 days
1 = 11 days
2 = 12 days
3 = 13 days
4 = 14 days
5 = 15 da ys
Message Format Receiver Format(s)
SumCheck (DTMF) DTMF, 1400 Hz only
CFSK III CFSK III only
Valid combinations of Receiver Format and Message Format are listed below.
3/1 Single or 3/1 Extended All formats, except CFSK III and DTMF, 1400 Hz
4/1 or 4/2 (2-digit reporting) Fast "A", 2300 Hz and Slow "B", 1400 Hz only
SYSTEM 238 Installation Manual
10
Command Locations 0B and 0C
Command Location 0B: Communications Control
Default Values
Digit Position (1): Delay Before Dial Time
0 = 0 secs
1 = 10 secs
2 = 20 secs
3 = 30 secs
0B
31 1008
(1) (2) (3) (4) (5) (6)
4 = 40 secs
5 = 50 secs
6 = 60 secs
7 = 70 secs
8 = 80 secs
9 = 90 secs
0 = 100 secs
1 = 110 secs
2 = 120 secs
3 = 130 secs
4 = 140 secs
5 = 150 secs
Digit Position (2): Dial Type
Digit Position (3): Enable Keypad Activated RPS
0 = No
1 = Yes; allows remote programming to start from on-site keypad command
Digit Position (4): RPS Enable
0 = No
1 = Yes; allows remote programming to start from off-premise location
Digit Position (5): Phone Ring Type
0 = Single ring; uniformly timed rings with long pauses between rings
1 = Double ring; rings twice quickly followed by a long pause then rings twice again
Digit Position (6): Dialing Attempts
5 = 5 tries
6 = 6 tries
7 = 7 tries
8 = 8 tries
1 = 1 try
2 = 2 tries
3 = 3 tries
4 = 4 tries
9 = 9 tries
0 = 10 tries
1 = 11 tries
2 = 12 tries
3 = 13 tries
4 = 14 tries
5 = 15 tries
1 = DTMF - Touch Tone (10/sec)
2 = DTMF (5/sec)
3 = Pulse (10/sec)
Command Location 0C: Account Number 1
(1) (2) (3) (4) (5) (6)
000000
C0
Default Values
Digit Positions (1) - (6): Account Number
Valid entries are 0 - F.
The Account Number is right justified. The last digit must be in Position (6).
The SYSTEM 238 will read the account number using:
Digit Positions (4) - (6) in 3-digit accounts
Digit Positions (3) - (6) in 4-digit accounts
Digit Positions (1) - (6) in 6-digit accounts
Fill all unused Digit Positions with 0's.
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
SYSTEM 238 Installation Manual
11
Command Locations 0D - 0F: Receiver #1 Phone Number
Order in which the numbers will be dialed
Command Location 0D
(1) (2) (3) (4) (5) (6)
Command Location 0E
(1) (2) (3) (4) (5) (6)
Command Location 0F
(1) (2) (3) (4) (5) (6)
Command Locations 0D - 10
Command Location 0D: Receiver #1 Phone Number (digits 1 - 6)
Digit Positions (1) - (6):
0 - 9 = dialing digits
0 = dial tone detect
2 = * (DTMF dialing only, not used in pulse dialing)
3 = # (DTMF dialing only, not used in pulse dialing)
4 = end of number
5 = 5 second delay
(1) (2) (3) (4) (5) (6)
0D
E00000
Default Values
Digit (1) is dialed first.
You must place a 4 (EON) after the last digit to be dialed. Fill in
remaining positions with "0". The zeroes will not be dialed.
Command Location 0E: Receiver #1 Phone Number (digits 7 - 12)
0E
(1) (2) (3) (4) (5) (6)
000000
Default Values
Command Location 0F: Receiver #1 Phone Number (digits 13 - 18)
0F
(1) (2) (3) (4) (5) (6)
000000
Default Values
Command Location 10: Account Number 2
10
(1) (2) (3) (4) (5) (6)
000000
Default Values
Digit Positions (1) - (6): Account Number 2
Valid entries are 0 - F.
Entries 0 and A both transmit 10 pulses. The Account Number is right justified.
The last digit must be in Position (6). The SYSTEM 238 will ignore unused Digit Positions:
Digit Positions (1) - (3) in 3-digit accounts
Digit Positions (1) & (2) in 4-digit accounts
Fill left hand unused portions with any digit values. They will not be used by the system.
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
Account Number 2 is used in
conjunction with Receiver Number 2
SYSTEM 238 Installation Manual
12
Command Locations 11 - 13: Receiver #2 Phone Number
Command Location 11
(1) (2) (3) (4) (5) (6)
Command Location 12
(1) (2) (3) (4) (5) (6)
Command Location 13
(1) (2) (3) (4) (5)
Command Location 11: Receiver #2 Phone Number (digits 1 - 6)
11
(1) (2) (3) (4) (5) (6)
E00000
Default Values
Digit Positions (1) - (6):
Digit (1) is dialed first.
You must place a 4 (EON) after the last digit to be dialed. Fill in
remaining positions with "0". The zeroes will not be dialed.
(6)
Order in which the numbers will be dialed
0 - 9 = dialing digits
0 = dial tone detect
2 = * (DTMF dialing only, not used in pulse dialing)
3 = # (DTMF dialing only, not used in pulse dialing)
4 = end of number
5 = 5 second delay
Command Locations 11 - 13
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
Command Location 12: Receiver #2 Phone Number (digits 7 - 12)
12
(1) (2) (3) (4) (6)
000000
Default Values
(5)
Command Location 13: Receiver #2 Phone Number (digits 13 - 18)
13
(1) (2) (3) (4) (5) (6)
000000
Default Values
SYSTEM 238 Installation Manual
13
Command Locations 14 - 16: RPS Phone Number
Command Location 14
(1) (2) (3) (4) (5) (6)
Command Location 15
(1) (2) (3) (4) (5) (6)
Command Location 16
(1) (2) (3) (4) (5) (6)
Order in which the numbers will be dialed
Command Locations 14 - 16
Command Location 14: RPS Phone Number (digits 1 - 6)
14
(1) (2) (3) (4) (5) (6)
E00000
Default Values
Digit Positions (1) - (6):
Digit (1) is dialed first.
You must place a 4 (EON) after the last digit to be dialed. Fill in
remaining positions with "0". The zeroes will not be dialed.
0 - 9 = dialing digits
0 = dial tone detect
2 = * (DTMF dialing only, not used in pulse dialing)
3 = # (DTMF dialing only, not used in pulse dialing)
4 = end of number
5 = 5 second delay
Command Location 15: RPS Phone Number (digits 7 - 12)
15
(1) (2) (3) (4) (6)
000000
Default Values
(5)
Command Location 16: RPS Phone Number (digits 13 - 18)
16
(1) (2) (3) (4) (5) (6)
000000
Default Values
NOTE:In order to utilize the Remote
Programming feature, CL 0B,
Digit Positions (3) and (4) must
also be programmed with YES.
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
SYSTEM 238 Installation Manual
14
Command Locations 17 - 1E: Loop Reporting Codes
17 = Loop 1
18 = Loop 2
19 = Loop 3
1A = Loop 4
Digit Positions (1) & (2): Alarm Reporting Code
Digit Positions (3) & (4): Restore Reporting Code
Digit Positions (5) & (6): Shunt Reporting Code
Only Position (1) is sent for 3/1 and 4/1 formats.
Positions (1) and (2) are sent for 3/1 Extended , 4/2, and CFSK formats.
Program 00 to disable Event Reporting for a loop.
If using 3/1 or 4/1 format, fill unused positions with "0".
(1) (2) (3) (4) (5) (6)
10E100
71
**Default Values
1B = Loop 5
1C = Loop 6
1D = Loop 7
1E = Loop 8
Command Locations 1F - 26: Loop Control
121323
F1
**Default Values
(1) (2) (3) (4) (5) (6)
1F = Loop 1
20 = Loop 2
21 = Loop 3
22 = Loop 4
23 = Loop 5
24 = Loop 6
25 = Loop 7
26 = Loop 8
Digit Position (1): Alarm Receiver Select
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (2): Loop Response Time
0 = 5 milliseconds
1 = 250 milliseconds
2 = 500 milliseconds
3 = 750 milliseconds
Digit Position (3): Loop Restore Type
0 = No Restoral Report sent
1 = Restoral sent when loop normal
2 = Restoral sent when loop normal and bell silences
3 = Restoral sent when loop normal and system disarmed
Digit Position (4): Loop Arming Type
1 = Interior: delayed during E/E delays
2 = Instant
3 = Delay
4 = Long Delay: delay two times as long
5 = Day/Instant: buzzer on day fault
6 = Day/Delay: buzzer on day fault
7 = Day/Instant with bell
8 = Day/Delay with bell
9 = 24 Hours: always armed
Digit Position (5): Loop Bell Type
1 = Temporal Code 3
2 = Steady
3 = Chirp
Digit Position (6): Loop CircuitType
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
**Default Values are different
for each loop. Refer to the
SYSTEM 238 Programming
Worksheet at the end of this
manual.
NOTE: A Loop programmed as type 4 or 5 will report
any open as a Trouble condition, regardless
of panel armed status.
1 = Normally Open Circuit
2 = Normally Closed Circuit
3 = End Of Line (EOL)
4 = Supervised, bell latched
5 = Supervised, bell not latched
Command Locations 17 - 26
4 = Silent with no LED
5 = Silent with LED
SYSTEM 238 Installation Manual
15
Command Location 27: Soft Zone A (EMERGENCY)
Digit Positions (1) and (2): Emergency Zone Code Report
(1) (2) (3) (4)
00 13
Default Values
27
Only Position (1) is sent for 3/1 and 4/1 formats.
Positions (1) and (2) are sent for 3/1 Extended, 4/2, and CFSK formats.
Program 00 to disable alarm reporting for Emergency zone.
Digit Position (3): Emergency Zone Receiver Select
Digit Position (4): Emergency Zone Loop Bell Type
1 = Temporal Code 3
2 = Steady
3 = Chirp
4 = Silent
Command Location 28: Soft Zone B (Fire)
(1) (2) (3) (4)
00 11
Default Values
28
Digit Position (4): Fire Zone Loop Bell Type
Digit Position (3): Fire Zone Receiver Select
Digit Positions (1) and (2): Fire Zone Report Code
Command Location 29: Soft Zone C (Police)
Digit Positions (1) and (2): Police Report Code
(1) (2) (3) (4)
00 12
Default Values
29
Digit Position (3): Police Zone Receiver Select
Digit Position (4): Police Loop Bell Type
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
NOTE: Command Location 2F Digit Position (4)
must be programmed to YES to enable
Soft Zones.
Refer to CL 27 for information about
programming this zone.
Refer to CL 27 for information about
programming this zone.
This Zone is identified by the "E" key
on the Alpha II and LED keypads.
This Zone is identified by the "F" key
on the Alpha II and LED keypads.
This Zone is identified by the "P" key
on the Alpha II and LED keypads.
Command Locations 27 - 29
SYSTEM 238 Installation Manual
16
Command Location 2A: Event Reporting
(1) (2) (3) (4) (5) (6)
11A1D1
A2
Default Values
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (2): Restore Receiver Select
See Digit Position (1) for programming options.
The panel will add a fixed extension digit when reporting in 3/1 Extended, 4/2, and CFSK formats.
Fixed codes are listed below.
Program a 0 to disable Unit Status Reporting.
See Digit Position (1) for programming options.
Valid entries are 0 - F.
The panel will add the User ID # as the second digit when reporting in
3/1 Extended, 4/2, and CFSK formats.
Program a 0 to disable Cancel Reports.
Digit Position (1): Shunt Receiver Select
Digit Position (3): Unit Status Report Code
Valid entries are 0 - F.
Digit Position (4): Unit Status Receiver Select
Digit Position (5): Cancel Report Code
Digit Position (6): Cancel Report Receiver Select
See Digit Position (1) for programming options.
1 = Low battery
2 = AC fail
3 = Bell fuse fail
4 = Loop trouble
5 = Failed to communicate
6 = Battery restore
UNIT STATUS FIXED EXTENSION CODES
7 = AC restore
8 = Bell fuse restore
9 = Loop trouble restore
A = not used
B = Watchdog reset
C = Completed programming
Command Location 2B: Test Report
(1) (2) (3) (4)
00 16
Default Values
2B
Digit Positions (1) and (2): Test Report Code
Valid entries are 0 - F.
Only Position (1) is sent for 3/1 and 4/1 formats.
Positions (1) and (2) are sent for 3/1 Extended, 4/2, and CFSK formats.
Program 00 to disable Test Reports.
Digit Positions (3): Test Report Receiver Select
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Digit Positions (4): Test Report Interval
1 = 1 hour
2 = 2 hours
3 = 4 hours
4 = 12 hours
5 = 24 hours
6 = 7 days
7 = 14 days
8 = 21 days
9 = 30 days
0 = 1 hour if armed
1 = 2 hours if armed
2 = 4 hours if armed
3 = 12 hours if armed
4 = 24 hours if armed
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
See also CL 17 - 1E
Digit Positons (5 & 6)
See also CL 17 - 1E
Digit Positions (3 & 4)
NOTE: CL A0 must be programmed
to correctly set time of test.
Command Location 2A and 2B
SYSTEM 238 Installation Manual
17
Command Location 2C: Opening and Closing Report Codes
Digit Position (1): Opening Report Code
(1) (2) (3) (4)
B1 C1
Default Values
2C
Valid entries are 0 - F.
The User ID # is transmitted after the opening code for 3/1 Extended, 4/2, and CFSK formats.
Program 0 to disable Opening Reports.
Digit Position (2): Opening Report Receiver Select
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (3): Closing Report Code
Valid entries are 0 - F.
The User ID # is transmitted after the opening code for 3/1 Extended, 4/2, and CFSK formats.
Program 0 to disable Closing Reports.
Digit Position (4): Closing Report Receiver Select
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Command Location 2D: Duress Report and Delays
Digit Position (1): Duress Report Code
Valid entries are 0 - F.
The User ID # will be reported as the second digit when reporting
in the 3/1 Extended, 4/2, or CFSK formats.
Program 0 to disable Duress Reports.
Default Values
(1) (2) (3) (4) (5)
03 620
2D
Digit Position (2): Duress Receiver Select
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (3): Entry Delay Time
1 = 110 secs
2 = 120 secs
3 = 130 secs
4 = 140 secs
5 = 150 secs
1 = 10 secs
2 = 20 secs
3 = 30 secs
4 = 40 secs
5 = 50 secs
6 = 60 secs
7 = 70 secs
8 = 80 secs
9 = 90 secs
0 = 100 secs
Digit Position (4): Exit Delay Time
1 = 110 secs
2 = 120 secs
3 = 130 secs
4 = 140 secs
5 = 150 secs
1 = 10 secs
2 = 20 secs
3 = 30 secs
4 = 40 secs
5 = 50 secs
Digit Position (5): Audible Time
1 = 2 min
2 = 5 min
3 = 10 min
4 = 15 min
5 = 30 min
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
6 = 60 secs
7 = 70 secs
8 = 80 secs
9 = 90 secs
0 = 100 secs
NOTE: To program delay times
greater than 150 secs, see
CL 1F - 26 Digit Position (4)
NOTE: To program delay times
greater than 150 secs, see
CL 1F - 26 Digit Position (4)
Command Locations 2C and 2D
SYSTEM 238 Installation Manual
18
Command Location 2E: Audible/Visual Switches
Digit Position (1): Entry Pre-alarm Enable
0 = No
1 = Yes: sounds keypad buzzers during entry delay
Digit Position (2): Exit Pre-alarm Enable
0 = No
1 = Yes: sounds keypad buzzers during exit delay
Digit Position (3): Bell Reverse Operation
0 = No
1 = Yes: supplies bell voltage in non-alarm state; Bell requires external power supply
Digit Position (4): Ring Back
Digit Position (5): Disable Loop LEDs
0 = No
1 = Yes: turns off keypad zone LEDs after 5 minutes
Default Values
(1) (2) (3) (4) (5)
10 001
2E
Command Location 2F: Unit Control
Digit Position (1): Local System Only
Default Values
(1) (2) (3) (4)
00 11
2F
Digit Position (2): Enable Daily Dynamic Battery Test
Digit Position (3): Enable Four Minute Power-Up Delay
Digit Position (4): Enable Soft Zone Operation
0 = No
1 = Yes: allows use of Emergency, Fire, and Police keys
0 = No
1 = Yes: disables all communications except RPS
0 = No
1 = Yes: tests battery under load every 24 hours
0 = No
1 = Yes: suppress alarms on power-up for 4 minutes
0 = No
1 = Yes: Automatic Bell test after arming (and Exit Delay has expired) for local or non-supervised
accounts; follows closing report for supervised accounts; sounds bell for 2 seconds.
Command Locations 2E and 2F
SYSTEM 238 Installation Manual
19
Command Locations 30 - 37: Loop Switches
30 = Loop 1
31 = Loop 2
32 = Loop 3
33 = Loop 4
Digit Position (1): Enable Door Chime
(1) (2) (3) (4)
00 00
3034 = Loop 5
35 = Loop 6
36 = Loop 7
37 = Loop 8
**Default Values are different for each loop.
Refer to the SYSTEM 238 Programming
Worksheet at the end of this manual for
other default values.
**Default Values
0 = No
1 = Yes: keypads beep 2 seconds when faulted (disarmed condition)
Digit Position (2): Allow Shunting of This Loop
0 = No: makes it a priority zone (not shuntable)
1 = Yes: authorized users can bypass or force arm
Digit Position (3): Allow Group Shunting for This Loop
0 = No
1 = Yes: include as part of group when performing Home Arming or Instant/Home Arming feature (See also pages 21 & 25)
Digit Position (4): Delay Before Dial
0 = No
1 = Yes: this loop will delay dialing on alarm for time programmed in 0B (1)
Command Location A0: Set Test Report Countdown Timer
Digit Position (1): Set Countdown Timer
A0
(1)
0 = 1/4 hour
1 = 1/2 hour
2 = 1 hour
3 = 2 hours
4 = 3 hours
5 = 4 hours
6 = 6 hours
7 = 8 hours
8 = 10 hours
9 = 12 hours
0 = 14 hours
1 = 16 hours
2 = 18 hours
3 = 20 hours
4 = 22 hours
5 = 24 hours
NOTE: Refer to CL 2B (4) for setting the
time interval between Reports.
Example: The time is 1500 hours (3:00 pm). You want the first Test Report to
transmit at 0100 hours (1:00 am). 3:00 pm + 10 hours = 1:00 am.
Program the value "8" in Memory Location A0.
PROGRAMMING CONVERSIONS
Hexadecimal Value
Key Strokes
A
B
C
D
E
F
0
1
2
3
4
5
Refer to CL 01 - 08 Digit Position (1) for
Arming Types (Authorization Levels).
Previously stored data is not displayed during programming.
This command will set the time when the first Test Report is transmitted to the central station. The
panel will use this transmission time each time it's powered up or the CPU is reset (unless Command
Location A0 is reprogrammed).
Command Locations 30 - 37 & A0
SYSTEM 238 Installation Manual
20
KEYPAD LABEL DRAWER
Each keypad comes with a Label Drawer and quick reference
operating label. Follow the diagram below to set up the Label Drawer
Example of drawer pulled
from the left
Example of drawer pulled
from the right
Regular maintenance and inspection (at least monthly) by the installer
and frequent testing by the user are vital to the continuous and
satisfying operation of any alarm system. The installer should assume
the responsibility for developing and offering a regular maintenance
program to the user, as well as acquainting the user with the proper
operation and limitations of the alarm system and its component parts.
Recommendations must include a specific program of regular
testing (at least weekly) to insure that the system is operating
properly at all times.
TELEPHONE LINE PROBLEMS
In the event of telephone line problems, disconnect the SYSTEM 238
by removing the modular connector plug from the Telco interface jack.
Do not disconnect the connection inside the SYSTEM 238
cabinet. Doing so will prevent the premise phones from operating. If
your phone works correctly after the control panel has been discon-
nected from the phone line, the control panel has a problem and should
be returned for repair.
If the phone does not work after you have disconnected the control
panel from the phone line, notify the telephone company and request
prompt repair. The user may not under any circumstance (in or
out of warranty) attempt any service or repairs on the SYSTEM 238.
The control panel must be returned to C&K SYSTEMS or an authorized
service agency for repairs.
DS1
WATCH
DOG
Watchdog Indicator
The SYSTEM 238 is protected by an advanced
circuit, called a Watch Dog circuit, that constantly
monitors the microprocessor.
As long as the panel has power and is operating
normally, the Watch Dog LED (DS1) on the circuit
board will flash. If the Watchdog circuit detects a failure, it will attempt
to reset the panel.
KEYPAD PLASTIC BASE
Rotate keypad base so
drawer slot faces the correct direction
Plastic
drawer
Plastic drawer and label slide into
drawer on back of keypad base
Plastic drawer
TESTING
Once the installation is complete, connect AC and DC power. Com-
plete programming, if required. Test all panel operations.
TO THE INSTALLER
If the panel does not operate properly, and the Watchdog LED no
longer flashes, call the C&K Technical Support Hotline at 1-800-
227-8065 in the U.S. or your local C&K Representative.
FCC NOTICE
WARNING: This device is intended to be installed by a profes-
sional alarm installer.
The user shall be cautioned that changes or modifications
not expressly approved by C&K SYSTEMS could void the
user's authority to operate the equipment.
This equipment complies with FCC Rules, Part 68.
On the outside of this equipment is a label that contains, among other information, the FCC
Registration Number and Ringer Equivalence Number (REN) for this equipment. If re-
quested, provide this information to your telephone company.
The REN is useful to determine the quantity of devices you may connect to your telephone
line and still have all of those devices ring when your number is called. In most, but not all
areas, the sum of the RENs devices should not exceed five (5.0). To be certain of the
number of devices you may connect to your line, as determined by the REN, you should
call your local telephone company to determine the maximum REN for your calling area.
Should you experience trouble with the telephone lines, disconnect the equipment from
the line to determine the source of the trouble. If it is determined that the equipment is
malfunctioning, discontinue its use until the malfunction has been corrected. Any repairs
or alterations made by the user to this equipment, or equipment malfunctions, may give the
telephone company cause to request the user to disconnect the equipment. Repairs to this
equipment should be made by an authorized agent of C&K Systems, Inc. Contact your
local alarm installation company for service.
Should this equipment cause harm to the telephone network, the telephone company may
temporarily discontinue your service. If possible, they will provide you with advance no-
tice. Otherwise they will notify you as soon as possible. The telephone company will also
advise you of changes in its facilities, equipment, operations or procedures which could
affect the operation of your equipment, allowing you the opportunity to maintain uninter-
rupted service. You will also be advised of your right to file a complaint with the FCC.
This equipment must not be used on party lines or coin operated phone lines.
FCC Part 15 Notice
This equipment has been tested and found to comply with the limits for Class B digital
devices, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reason-
able protection against harmful interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy, and if not in-
stalled and used in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference will not occur in
a particular installation.
If this equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
Reorient the radio/television antenna;
Connect the AC transformer to a different outlet so that the equipment and radio/tele-
vision are on different branch circuits;
Relocate the equipment with respect to the radio/television;
Consult the dealer or an experienced radio/television technician for help.
FCC Registration Number: C2DCHN-18741-AL-E
Ringer Equivalence: 0.3B
CANADIAN EMISSION REQUIREMENTS
This Class B digital apparatus meets all requirements of the Canadian Interference-
Causing Equipment Regulations.
Cet appareil numérique de la classe B respecte toute les exigences du Règlement sur
le matériel brouilleur du Canada.
1. Fill in the zone descriptions inside the label.
2. Mark "Y" or "N" to indicate if zones can be bypassed or not.
3. Determine if the drawer will slide from the right or left.
4. Peel the cover off the drawer glue.
5. Align the edge of the label with the edge of the drawer. Center
the label top to bottom.
6. Press the label onto the glue. Avoid trapping air
bubbles under the label.
7. Slide the drawer/label into the slot on the back of the
keypadbase.
21
SYSTEM 238 Installation Manual
Alpha Keypad Programming Start Programming the Keypad [Installer Combination] [*] [0] [1] [#]
Alpha Keypad Test [*] [6] [7] [#]
Kill/Revive Panel [Installer Combination] [*] [6] [9] [#]
Panel Programming Start Programming the Panel [Installer Combination] [*] [0] [#]
Function Comments Keystroke Sequence
The following Keypad Commands are Installer Only Commands:
Keypad Operation Command Summary
The majority of the keypad commands apply equally to the LED and Alpha II keypads. Some keypad commands, however, apply
to the LCD keypad only.
The following Keypad Commands apply to both the LED and Alpha II keypads:
Function Comments Keystroke Sequence
Arm/Disarm Delays active [Combination] [#]
Bypass Zone (n) [n] is zone # 1 - 8; Combo may be required [Combination] [Bypass] [n] [#]
Chime On/Off Combo may be required [Combination] [*] [5] [#]
Change Combo (via Must be done by User #1 [Master Combo] [*] [0] [#]
Master Code) [New Combo] [#] [New Combo] [#]
Clear Alarm Memory [*] [1] [#]
Exit Programming [*] [#]
Fire Alarm Keypad activated [F] (Hold for 3 seconds)
Group Bypass and Arm Arms system and all zones programmed for [Combination] [*] [4] [#]
group bypass, CL 30 - 3F, Digit Position (3),
are shunted simultaneously; Combo may be
required. (Also called Home Arming)
Group Bypass and Instant Same as Group Bypass (above) except system [Combination] [*] [4] [7] [#] or
Arm is Instant Armed (Exit Delay operates normally, [Combination] [*] [7] [4] [#]
upon expiration of Exit Delay, all delayed zones
are converted to Instant - No Entry Delay.
Combo may be required. (Also called
Instant/Home Arming)
Instant Arm Arms system and delayed zones are converted [Combination] [*] [7] [#]
to Instant (Exit Delay active, No Entry Delay);
Combo may be required
Keypad Activated RPS If enabled, CL 0B(3); Combo may be required [Combination] [*] [0] [2] [#]
Medical Alarm Keypad activated [E] (Hold for 3 seconds)
Police/Panic Alarm Keypad activated [P] (Hold for 3 seconds)
Reset Aux Power If resettable devices are connected to [*] [6] [2] [#]
Terminals 5 and 6 (also resets devices
connected to Loop 8 (e.g. 2-wire smoke
detectors)
Reset Panel [Master Combination] [*] [6] [8] [#]
Test - Battery Use after correcting Low Battery problem [*] [6] [4] [#]
Test - Bells Combo may be required [Combination] [*] [6] [3] [#]
Test - Central Station Combo may be required [Combination] [*] [6] [1] [#]
Test - Local Walk Test [*] [6] [0] [#]
NOTE: For additional information about Combination Command requirements, see page 24 and CL 09 (2).
Error Tones Toggle On/Off [*] [5] [4] [#]
Audible Feedback Toggle [*] [5] [1] [#]
Backlight Toggle On/Off [*] [8] [#]
Display Keypad Model [*] [9] [#]
& Revision Number
Chime Toggle [*] [5] [3] [#]
Pre-warn Toggle On/Off [*] [5] [2] [#]
Function Comments Keystroke Sequence
The following Keypad Commands apply to the Alpha II keypad only:
SYSTEM 238 Installation Manual
22
Survey of Most Common Questions
The following is a summary of the questions most frequently asked of our Technical Support Department.
Trouble LED Power LED Zone LED's Cause
Flash Slow On Off Watchdog
On On Flash Slow Zone Trouble
On Off Off AC Failure
On Flash Slow Off Low Battery
On On Off System Trouble (Bell Fuse or Comm Fail.)
Question: How do I program the panel with the LED keypad?
Answer: To program with the LED keypad, enter the Command Location to be programmed, the Data to be pro-
grammed and the press the [#] key. (See also pages 6 - 7.)
For Example: To program User #2 with the ability to Arm only, No Reports and No Shunting; and
a PIN of 2543, enter the following keystrokes:
CL Arm Type PIN (w/EON) Write Data
[0][2] [1] [2][5][4][3][*][4] [#]
NOTE: The first digit of the User Code MUST be the same as the User Number.
Question: How do I access Alpha Keypad Programming to enter Zone Labels?
Answer: To begin Alpha Keypad Programming (you cannot program the LED keypad), enter [Installer Combination]
[*] [0] [1] [#]. Then scroll to the desired message location. (See also pages 7 - 8.)
Question: How do I interpret a Trouble on the LED keypad? How do I clear a Trouble on the LED keypad?
Answer: A number of conditions may cause the Trouble LED to light. See the chart below for additional information.
Question: How do I enter hexadecimal numbers when using keypad programming?
Answer: Hexadecimal values are entered through the use of the [*] key and one of the digits [0] - [5]. For additional
help with entering hexadecimal numbers, refer to page 7. The hexadecimal conversion chart is also found at
various locations throughout the programming section of the manual.
Question: What is an "Interface error 1" and how do I correct the error?
Answer: This error is caused by a problem with the Data line (Green wire) between the panel and the keypad. Check
the connection to ensure that the wire is not pinched or loose. Also try disconnecting all keypads from the
panel (one at a time), resetting the panel after each keypad is removed. Remember, to reset the panel press:
[Master Combination] [*] [6] [8] [#].
Question: How do I reset Alarm Memory?
Answer: To Clear Alarm Memory, press [*] [1] [#].
Question: How do I address an Alpha Keypad for the first time?
Answer: If you have an Alpha keypad that has never been addressed, when power is initially applied, the display will
read KEYPAD ADDRESS?. To enter the address, simply press a number between 0 and 7. Remove panel
power for 3 seconds and then re-apply power to reset the system. For additional information about Keypad
addressing, see page 5.
NOTE: If operating at or near the limit of AUX Power and Keypad Power, you may need to remove
power for up to 30 seconds in order for the system to reset properly.
Question: Why do my loops fail to respond after changing the programming?
Answer: In order for the panel to recognize the programming changes for the loops, either the loops have to be
tripped and restored or the panel must be reset ( [Master Combination] [*] [6] [8] [#] ).
23
SYSTEM 238 Installation Manual
Question: How do I interpret the Unit Status Reports? Can the codes be changed?
Answer: The Reporting Codes for the Unit Status Report is a two-digit code. The first digit is programmed into CL 2A
Digit Position (3) and may be any value from 0 - F. The second digit is fixed by the firmware and cannot be
changed. Please note that programming a 0 into 2A (3) will disable the report and no Unit Status information
will be sent. Additional information about Unit Status Reporting Codes can be found on page 17 in the
programming section.
Question: How do I enter Receiver and RPS Phone Numbers? Why do I have to enter the E at the end of the number?
Answer: The System 2316 is designed to handle phone numbers up to 18 digits long, but the firmware can only handle
6 digits per Command Location. This means that 3 Command Locations are required to store a phone number.
With variations in number length and special characters which may need to be included, the software needs
some method of determining the end of the number. The E (entered by pressing [*][4]) tells the software that it
has reached the end of the phone number and to ignore any additional digits.
For Example: To program the panel for Receiver #1 with a phone number of 555-1212 and disable
the call waiting feature using *70, enter the following sequence:
Command Location 0D
(1) (2) (3) (4) (5) (6)
Command Location 0E
(1) (2) (3) (4) (5) (6)
Command Location 0F
(1) (2) (3) (4) (5) (6)
C7
0555 12
12E
00
0
0
0
00
NOTE: Entering [*] [2] in CL 0D (1) will display the value "C" and entering [*] [4] in CL 0E (5) will display the value "E".
Question: How can I correct the problem of two Alpha keypads with the same address?
Answer: When two keypads have been given the same address, a conflict occurs on the data bus since two keypads
are trying to communicate at the same time. The only way to correct the problem is to disconnect both keypads
and then re-address one of them, making sure that the address is not used by any other keypad. To re-address
the keypad, enter Alpha Keypad Programming ( [Installer Combination] [*] [0] [1] [#] ) and scroll backward
one step ( [*] [BYPASS] ). Then enter the new address. Don't forget to reset the panel ([Master Combination]
[*] [6] [8] ]#]) after changing the address, so the panel knows how to properly address the keypad. For
additional information about keypad addressing, see page 5.
Question: Why can't my panel communicate with the Central Station?
Answer: There are several reasons for the panel not communicating. The first place to look is CL 2F (1). This is the Unit
Control, if Digit Position (1) is programmed with a 1, all communication except RPS is disabled. If 2F (1) is
programmed with a 0, check to ensure that all of the following parameters are properly set:
Account Number 1 is programmed into CL 0C
Receiver #1 Phone Number is correctly programmed into CL 0D - 0F
Receiver Format and Message Format agree CL 0A
Communication Control (CL 0B) is correctly programmed
The RJ-31X jack is correctly wired (terminals 4 & 5 are not switched with 1 & 8)
Question: How do I disarm my panel if I accidently locked myself out by programming my user code as Arm Only?
Answer: The only way to correct this problem is to access the panel through Remote Programming (RPS) or Direct
Connect (also RPS) and disarm the panel. Then use the remote programming to re-program the panel. For
additional information about RPS, see the Commander II/Monitor II Operating Manual.
Question: Why doesn't my keypad respond? The Power LED is lit, but nothing happens.
Answer: The panel may be in the KILL mode. On the LED keypad, only the Power LED will be lit. On the Alpha II
keypad, the Power LED will be lit and the Service Message, if programmed, will be displayed. To restore the
panel, press [Installer Combination] [*] [6] [9] [#].
SYSTEM 238 Installation Manual
24
The recommendations contained in this section are designed to assist you in reducing false alarms. The first column
contains the Command Locations and Digit Positions in parentheses ( ). The second column is the recommended program
option followed by a brief explanation.
Recommendations for Reducing False Alarms
Program Option CL Program Function Comments
Arming/Combination 09 (2) Combination This feature is enabled to prevent unauthorized users from
Options Command activating certain keypad functions. When activated, this
command will require a valid User Combination to perform such
functions as Bypassing a Zone, Group Bypassing, Keypad
Activated RPS, Central Station and Bell Testing, and Instant
Arming. For additional assistance with commands requiring User
Combinations, see page 21 (Command Summary).
Arming/Combination 09 (4) Chirp Alert This option minimizes the possibility of creating an error when
Options exiting. The system is armed in the normal manner and the user
exits through the delayed exit door. If the door does not close
properly (returning the loop to the normal state), the system will
transition from the Exit Delay to the Entrance Delay upon the
completion of the Exit Delay time the Bell will chirp , alerting the user
to the error in arming the system.
Loop Control 1F - 26 (2) Loop Response This option determines the response time of the loop itself. It acts
Time as a buffer on the loop to minimize the possibility of fast acting
sensors, such as swingers on window foil, producing false alarms.
Loop Control 1F - 26 (3) Loop Restore This option is used in conjunction with CL 17 - 1E Digit Positions
Type (3 & 4), Restore Reporting Code, and CL 2A (2), Restore Receiver
Select. The panel can be programmed to send a Restoral Report
only when the loop is normal and the system is disarmed. With this
arrangement, any loop which is triggered multiple times while
armed will only send one alarm report until the system is disarmed.
This prevents the system from tieing up the central station receivers
and the phone line with continuous alarm and restoral reports.
Loop Control 1F - 26 (4) Loop Arming There may be occassion where it is desirable to program all doors
Type and interior points as delayed. Or you may need to program
interior zones to be delayed only during the Entry/Exit Delay
Time. This Command Location allows a variety of Arming Types
to help minimize false alarms.
Event Reporting 2A (5 & 6) Cancel Report This feature should always be enabled on reporting systems,
Code/Cancel especially if the system does not send Opening and Closing
ReportReceiver Reports. A Cancel Report is sent to the monitoring station in the
Select event that an Authorized User clears the alarm while the bell is
still active. The Cancel Report Code (Digit Position 5) is actually
a two-digit code with the first digit being programmed by the
installer and the second digit being the User ID # when the report
is sent. Digit Position (6) determines which receiver gets the
Cancel Report.
25
SYSTEM 238 Installation Manual
Program Option CL Program Function Comments
Audible/Visual 2E (1 & 2) Entry/Exit If Digit Postition (1) is programmed for Entry Pre-Alarm, the
Switches Pre-Alarm keypad will beep for the amount of time programmed for the Entry
Delay Time (CL 2D (3)). If Digit Position (2) is programmed for
Exit Pre-Alarm, the keypad will beep for the time programmed
into CL 2D (4), Exit Delay Time. The speed at which the keypad
beeps will increase during the last 10 seconds of the Delay time.
Alpha II keypads will display a bar graph in addition to the audible
tone.
Unit Control 2F (3) Enable 4-minute Suppresses all trouble and alarm reports for a period of four
Power-Up minutes after power is initially applied to the panel. This allows
Delay the sensors, such as PIR's time to stabilize when initializing or
prevents powered devices, such as smoke detectors, from
sending alarms when first starting panel with a dead battery or no
battery connected.
Loop Switches 30 - 37 (3) Allow Group This allows multiple loops to be shunted simultaneously with a
Shunting single keypad command. This is typically done on all interior
loops in a system.
Loop Switches 30 - 37 (4) Delay Before Dial This option programs the loops to have a delay after they are
triggered to allow the User time to shut down the system in the
event of an accidental triggering of the zone. The amount of time
is determined by the value programmed into CL 0B Digit Position
(1). The time delay may be between 10 and 150 seconds, in 10
second intervals.
SYSTEM 238 Installation Manual
26
Intruders may gain access through unprotected openings or
have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
Intrusion detectors, smoke detectors, and many sensing de-
vices will not operate without power. Devices powered by AC
will not work if their AC power supply is off for any reason and
their back-up batteries are missing, dead, or improperly
installed.
Alarm warning devices such as sirens, bells, and horns may not
alert people or wake up sleepers if they are located on the other
side of closed or partly closed doors. If warning devices are
on a different level of the residence from the bedrooms, they
are less likely to waken or alert people inside the bedrooms.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are subject to
compromise by sophisticated methods of attack.
.
.
.
.
While the SYSTEM 238 is an advanced design security system, it does
not offer guaranteed protection against burglary, fire, or other losses.
Any alarm system, whether commercial or residential, is subject to
compromise or failure-to-warn for a variety of reasons. These include:
THE LIMITATIONS OF YOUR ALARM SYSTEM
Smoke detectors used in conjunction with the alarm system
may not sense fires that start where smoke cannot reach the
detectors, such as chimneys, walls, or roofs, or on the other side
of closed doors. Smoke detectors also may not sense a fire on
another level of the residence or building. A second floor
detector, for example, may not sense a first floor or basement
fire. Finally, smoke detectors have sensing limitations. No
smoke detector can sense every kind of fire every time. In
general, detectors may not always warn you about fires caused
by carelessness and safety hazards, like smoking in bed, violent
explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, children playing with
matches, arson, etc.
The most common cause of an alarm system not functioning
properly when an intrusion or fire occurs is inadequate
maintenace. Your alarm system should be tested weekly to
make sure all sensors are operating properly. The SYSTEM
238 panel and keypads should also be tested.
.
.
.
Installing an alarm system may make you eligible for lower
insurance rates, but an alarm system is not a substitute for
insurance. Homeowners, property owners, and renters should
continue to insure their lives and property.
C&K is a registered trademark of C&K Components, Inc.
Copyright 1998 C&K SYSTEMS, Inc.
All Rights Reserved
P/N 5-051-162-00 Rev K
Note: The contents of this manual have been revised. For
your convenience, dashed lines have been added to
the margins of the document to show the locations of
the changes.
http://www.cksys.com
SYSTEM 238 Programming Worksheet
E
00000
10
0
Account #2
0000
11
0
Phone #2 (1st 6 digits)
00000
13
0
(Last 6 digits)
00000
12
0
(Middle 6 digits)
E0 0 0 0
14
0
RPS Phone (1st 6 digits)
00000
16
0
(Last 6 digits)
00000
15
0
(Middle 6 digits)
E
00000
0C
0
Account #1
0000
0D
0
Phone #1 (1st 6 digits)
00000
0F
0
(Last 6 digits)
00000
0E
0
(Middle 6 digits)
BATTERY VOLTS
Under load - AC off:
CONTROL LOCATION:
BREAKER # AND LOCATION:
Client: SYSTEM 238 Phone Number:
Date: Control Location:Installer:
Address:
VOLTS
AC volts (term 1 and 2):
AUX POWER VOLTS
(term 5 and 6):
CURRENT
Keypads (term 6 and 8):
SWITCHED AUX
(term 5 and 6):
+
+
UNSWITCHED AUX
(term 6 and 7):
LOOP 8 POWERED
DEVICES
(term 21 and 22):
+
TOTAL
(500 mA allowed):
=
Address Location
ALPHA KEYPADS
0
2
3
7
5
4
6
1
03110
0B
8
Communications
Control
09
0011
Arm/Combination
Option
0A
1212
Communications
Formats
User #8 -Guest
Name:
07
7
97E000
User #7
Name:
08
8
98E000
05
5
95E000
User #5
Name:
06
6
96E000
User #6
Name:
03
3
93E000
User #3
Name:
04
4
94E000
User #4
Name:
012345
00
0
Installer
Combination
91234
01
E
1
User #1 - Master
Name:
02
2
92E000
User #2
Name:
12132
1F
3
Loop 1
Control
Description Volts Ohms
30E300
Loop 8
Codes
10E10
17
0
Loop 1
Codes
19
Loop 3
Codes
1B
500
Loop 5
Codes
1D
70 700
Loop 7
Codes
18
20 200
Loop 2
Codes
1A
40 400
Loop 4
Codes
1C
60 600
Loop 6
Codes
1E
80 800
50E
E
E
E
E
E
30
0000
Loop 1
Switches
32
0100
Loop 3
Switches
34
0100
Loop 5
Switches
36
0000
Loop 7
Switches
31
0100
Loop 2
Switches
33
0100
Loop 4
Switches
35
0100
Loop 6
Switches
37
0000
Loop 8
Switches
11A1D
2A
1
Event
Reports
2C
B1C1
11000
2E
Opening/Closing
Reports
Audible/Visual
Switches
2B
0016
00362
2D
Test
Report
Duress/
Delays
2F
1001
Unit
Control
27
0013
Emergency
Zone
29
0012
Police
Zone
28
0011
Fire
Zone
12122
20
3
Loop 2
Control
12122
21
3
Loop 3
Control
12122
22
3
Loop 4
Control
12112
23
3
Loop 5
Control
12112
24
3
Loop 6
Control
12193
25
3
Loop 7
Control
12191
26
5
Loop 8
Control

